HSL-AI16AO2 Calibration 117
Appendix C HSL-AI16AO2 Calibration
C.1 Before you proceed
Before calibrating the HSL-AI16AO2-M-VV and HSL-AI16AO2-M-
AV, take note of the following:
1. Make sure that the signal type is single-ended. You may
set this via the jumper.
2. Use a precise calibrator that can generate a precise 5 V.
3. Check the status text to know if the calibration is suc-
cessful or not.
4. Refer to the analog input field configuration below.