Command Set
3.9 Digital Input (6024 only)
@Description
Read the digital input channel value.
@Syntax
$(Addr)8<CR>
$
Command leading code.
(Addr)
Address ID
8
Digital data input command.
@Response
!(DataIn)0000<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(DataIn) Value of digital input. (2-character)
@Example
User command: $308<CR>
Response: !320000<CR>
!
Command is valid.
32
32 (00110010) means digital output channel 1, 4, 5
are ON, channel 0, 2, 3, 6 are OFF.
0000
No used