Command Set
27
3.4 Read Module Name
@Description
Read module name of NuDAM at specified address.
@Syntax
$(Addr)M<CR>
$
Command leading code.
(Addr)
Address ID.
M
Read module name.
@Response
!(Addr)(ModuleName) <CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
(ModuleName)
NuDAM module‘s name would be ’6021‘.
4 characters
@Example
User command: $18M<CR>
Response: !186021<CR>
!
Command is valid.
18
Address ID is 18 (Hex).
6021
ND-6021 (It is a analog output module)